(论文 字数:8578页数:9)摘要:本文参照我国电力系统保护装置的设计原则,结合自直流输电技术投入商业运行后,出现的微机控制保护装置特点,对“葛南”直流输电系统、“天广”直流输电系统,以及“三常”直流输电系统三个高压直流输电系统的控制保护装置的冗余配置进行了评价。本文认为,必须明确被控制和保护的设备与控制保护装置本身的不同冗余概念;“三取二”配置是微机保护设备的最佳冗余配置,因为它能有效地解决保护装置本身电子元件故障造成的误动与拒动。 本文对直流输电各种二次系统冗余方式优、缺点进行的论述,仅供直流输电系统,以及电力系统控制保护装置的设计和运行维护参考。
关键字:系统的可靠性,电子设备冗余,控制保护配置
The Redundancy of the Device of Control and Protection in HVDC
Abstract :This paper is a evaluate the redundancy of the device of control and protection in “Ge-Nan” and “Tian-Guang” and “Long-Zheng” HVDC link according to the feature of microcomputer control device and refer to the arrange principle of AC protection. It think that the three selected two is the best arrange in DC protection device. The reliability of the different redundancy ways is analyzed. The advantage and weak of redundancy at the different HVDC link in the China were being present. The evaluate will be referred by other HVDC link and AC system protection designs.
Keyword: Reliability of System, Redundancy of Electronic device, Arrange of control and protection
目录
一、前言 二、电力系统保护的配置原则 三、直流控制保护装置的冗余配置 四、结论
一.前言 对于任何系统及设备,它们的高可靠性和可用率是人们所期望的。为了提高一个系统或设备的可靠性,必须保证组成系统的各个设备及元件的高可用率,并且有相应的冗余,防止个别元件损坏,造成系统或设备不能运行。 电力系统的高可靠性,除了由一次设备的性能质量和系统结构的稳定性保证外,还要由二次控制保护系统保证;即:二次系统对一次系统设备进行控制和保护,自动切除故障部分,避免系统停运或设备损坏。 二次系统是由大量电子元件及微处理器构成,它们的可靠性是整个系统可靠性的重要组成部分。因此,控制保护系统除了保证相关一次设备的可靠性外,必须确保本身的高可靠性,这是本文重点讨论的问题。 由于控制保护系统使用了大量的电子元件,容易发生故障,仅一套设备不能保证系统长期运行的可靠性;因此,需要冗余配置。在当今电子技术高速发展时期,大规模集成电路和实时微处理器的广泛应用,给控制保护设备本身的冗余提供了可靠的技术保证。冗余方式的选择,需要根据具体设备在系统中的作用和对可靠性、经济性的影响来确定。 |